For applications in hazardous areas
High protection rating for the requirements of harsh industrial environments
Metal sensing face for heavy duty
Special mechanical stability ensures high plant safety
Clearly visible indication of the switching status
Product characteristics
Electrical design | PNP |
---|
Output function | normally open |
---|
Sensing range [mm] | 12 |
---|
Housing | threaded type |
---|
Dimensions [mm] | M18 x 1 / L = 70 |
---|
Application
Special feature | Gold-plated contacts; Increased sensing range; Full-metal housing |
---|
Pressure rating [bar] | 100 |
---|
Note on pressure rating | sensing face |
---|
Electrical data
Operating voltage [V] | 10...30 DC |
---|
Current consumption [mA] | < 25 |
---|
Protection class | III |
---|
Reverse polarity protection | yes |
---|
Outputs
Electrical design | PNP |
---|
Output function | normally open |
---|
Max. voltage drop switching output DC [V] | 2.5 |
---|
Permanent current rating of switching output DC [mA] | 100 |
---|
Switching frequency DC [Hz] | 500 |
---|
Short-circuit protection | yes |
---|
Overload protection | yes |
---|
Detection zone
Sensing range [mm] | 12 |
---|
Real sensing range Sr [mm] | 12 ± 10 % |
---|
Operating distance [mm] | 0...9.72 |
---|
Increased sensing range | yes |
---|
Accuracy / deviations
Correction factor | steel: 1 / stainless steel: 1 / brass: 0.9 / aluminium: 0.8 / copper: 0.5 |
---|
Hysteresis [% of Sr] | 1...20 |
---|
Switch point drift [% of Sr] | -10...10 |
---|
Operating conditions
Ambient temperature [°C] | -40...60 |
---|
Protection | IP 67; (when used outside the hazardous area: IP 65, IP 67, IP 68, IP 69K) |
---|
Tests / approvals
ATEX marking | II 3G Ex ec IIC T4 Gc X; II 3D Ex tc IIIC T95°C Dc X |
---|
EMC | EN 61000-4-2 ESD4 kV CD / 8 kV ADEN 61000-4-3 HF radiated10 V/mEN 61000-4-4 Burst2 kVEN 61000-4-6 HF conducted10 VEN 55011class B |
---|
Impact resistance | EN 60068-2-75 Ehc1 J |
---|
Vibration resistance | EN 60068-2-6 Fc20 g (10...3000 Hz) / 50 sweep cycles, 1 octave per minute, in 3 axes |
---|
Shock resistance | EN 60068-2-27 Ea100 g 11 ms half-sine; 3 shocks each in every direction of the 3 coordinate axes |
---|
Continuous shock resistance | EN 60068-2-27 Ea40 g 6 ms; 4000 shocks each in every direction of the 3 coordinate axes |
---|
Fast temperature change | EN 60068-2-14 NaTA = -40°C; TB = 85°C; t1 = 30 min; t2 = 10 s 50 cycles |
---|
Salt spray test | EN 60068-2-52 Kbseverity level 5 (4 test cycles) |
---|
MTTF [years] | 1352 |
---|
Mechanical data
Weight [g] | 79.5 |
---|
Housing | threaded type |
---|
Mounting | non-flush mountable |
---|
Dimensions [mm] | M18 x 1 / L = 70 |
---|
Thread designation | M18 x 1 |
---|
Materials | stainless steel (1.4404 / 316L); PEI; lock nuts: brass white bronze coated |
---|
Tightening torque [Nm] | 50 |
---|
Full-metal housing | yes |
---|
Displays / operating elements
Display | switching status4 x 90° LED, yellow |
---|
Accessories
Items supplied | lock nuts: 2 |
---|
Remarks
Remarks | To maintain the EMC data:Equalise potential by connecting the sensor housing to the machine earth. |
---|
Pack quantity | 1 pcs. |
---|
Electrical connection - plug
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |
---|